Samsung AC018BNJDCH/AA Split System Unit, 208-230 V, 20.1 A, 17000 Btu/hr, 19000 Btu/hr BTU, 1 ph -Phase

Manufacturer: Samsung
Part #: SAMCNH18JDB
Customer Part #:
Login for Availability
Login for Price
Additional Information      :      Inverter Driven, Twin BLDC Rotary Compressor, R-410A Refrigerant, 1/4 in, 1/2 in Connection, Console Single-Zone Duct
Amperage Rating      :      20.1 A
BTU Rating      :      17000 Btu/hr, 19000 Btu/hr
CFM Rating      :      261 cfm, 297 cfm, 332 cfm
Drive Type      :      Inverter
EER Rating      :      10
Frequency Rating      :      60 Hz
Fuse Rating      :      25 A
HSPF Rating      :      7.8
Number of Fan Speeds      :      3
Overall Height      :      7-13/16 in
Overall Length      :      24-7/16 in
Overall Width      :      28-3/8 in
Phase      :      1 ph
Power Rating      :      125 W
SEER Rating      :      18.8
Sound Level      :      35 dBA, 39 dBA, 43 dBA
Temperature Rating      :      61 to 90 deg F, <=86 deg F
Voltage Rating      :      208-230 V

The console unit can be installed sitting on the floor or hanging low on a wall, making it a great option for replacing a radiator in order to provide both heating and cooling in almost any space.

Samsung Split System Unit, 208-230 V, 20.1 A, 125 W, 60 Hz, 1 ph, 3 Number of Fan Speeds, 17000 Btu/hr, 19000 Btu/hr, 261 cfm, 297 cfm, 332 cfm CFM Rating, 10 EER, 18.8 SEER, HSPF: 7.8, 25 A Fuse, Inverter Drive, 35 dBA, 39 dBA, 43 dBA, 61 to 90 deg F, <=86 deg F, 24-7/16 in Overall Length, 28-3/8 in Overall Width, 7-13/16 in Overall Height, Additional Information: Inverter Driven, Twin BLDC Rotary Compressor, R-410A Refrigerant, 1/4 in, 1/2 in Connection, Console Single-Zone Duct

  • The outdoor unit shall supply power to indoor unit via 14 AWG x 3 power wire
  • High voltage terminal block temperature sensor to disable unit in the event of power connection overheating
  • Auto-restart after power loss
  • Soft start compressor minimizing current inrush
  • Base pan heater equipped as standard
  • All heat exchangers shall be mechanically bonded aluminum fin to copper tube
  • The condensing unit heat exchanger salt spray test method ISO 9227 the heat exchanger showed no unusual rust or corrosion development to 3000 hr
  • The front panel shall have LED indicator lights, touch controls, IR receiver and one-motorized louver
  • Indoor fan is a single turbo type
  • The unit shall discharge cool air from the upper outlet louver (motorized) while in cooling mode and warm air from the upper and lower (manual adjustment only) outlets while in heating mode
  • Three-fan speed settings and auto setting
  • Washable filter as standard
  • Control wiring shall be two 16 AWG
  • Wireless controller included as standard
  • Wired controllers must be purchased separately
  • Dual-set temperature support when connected to MWR-WG00UN advanced wired controller or central control options
  • No additional interface modules/adapters are required when connecting to Samsung central control options
  • The unit shall be operated via a wireless or wired remote control with DDC type signal
  • The compressor shall be hermetically sealed, inverter controlled BLDC rotary type
  • Refrigerant flow shall be controlled by an electronic expansion valve at outdoor unit